Measuring Current

Power Meters


Solar-Log™ PRO380-Mod


Solar-Log™ PRO380-Mod-CT


Solar-Log™ PRO1 1-phase


Iskra power meter 1-phase - S0


Solar-Log™
Utility Meter

Measuring Current Effectively

Power Meters

Depending on their use, different operating modes can be configured in the Solar-Log™ for the meters. It is possible to record production output (generator), consumption (consumption or bi-directional meter*) and sub-consumer values such as battery charge levels. Due to the operating modes, the compatible meters can be used for a wide range of possible applications.

*Bi-directional recording of the consumption with a single phase Iskra energy meter or Solar-Log™ PRO1 is not possible.


Video: Solar-Log™ PRO380–CT – Adjusting the Converter Ratio. Only valid for meters with the firmware 1.19.


Video: Solar-Log™ PRO380–Mod–CT – Adjusting the Converter Ratio. Only valid for meters with the firmware 2.19 or higher.

Technical dataSolar-Log™ PRO380-
Mod, three-phase current meter, MID (calibrated),
RS485
Solar-Log™ PRO380-Mod-CT, Transformer-connected meter,
RS485, three-phase
Solar-Log™ PRO1 singlephase
energy meter,
1-phase, MID (calibrated),
RS485
Iskra
uncalibrated,
1-phase, S0
ConnectionsExternal tariff switching/
4-pinr S0-Out für A+, A- /
2-pin Modbus Interface
2 x S0 (forward, reverse)
RS485 (Modbus)
External tariff switching
2-pin S0-Out
2-pin Modbus interface
6-pin S0-In /
Out connector /
maximum cable
length 10 m
Direct connection100 A6 A (Transformer input)45 A80 A
InterfacesS0/RS485 max. 32 unitsS0/RS485S0/RS485 maximum 32 unitsS0
Voltage UN3 x 230/400V AC
(-15% - +10%)
3 x 230 / 400 V AC
(100/173V - 270/468V)
230 V AC230 V
-20 % – +15 %
Measuring range20 mA - 100 A6 mA - 5 A20 mA - 45 A4 mA – 80 A
Self-consumption<2 W/Phase - < 10VA/Phase< 2 W per phase -< 10VA per phase< 10 VA - < 2 W per phase< 8 VA
Start-up current20 mA3 mA20 mA20 mA
Power frequency50Hz50 Hz 50 Hz50 Hz / 60 Hz
Dimensions (w x h x d) in mm70 x 140 x 6370 x 140 x 6317,5 x 117 x 6336.5 x 100.5 x 65
wire diameter25 mm2Max. 10 mm2 or
2.5 mm2 (Additional terminals)
Maximum 10 mm² or
2,5 mm² (Additional terminals)
2.5 - 10 mm²
Protection levelIP51IP51IP51IP20
LCD display6 + 2 Digits5 + 3 Digits4 + 2 Digits2 x 7-Digit-LCD
S0 pulse1000 p / kWh, 30 ms10000 Imp/kWh, 30 ms2 000 Imp/kWh, RA
= 0,5 Wh/Imp
1000 p / kWh
Misc.Blue illuminated display     One additional resettable counter Display for activ and reachtive power consumption intwo energy flow directions Display: I, U, P, S, F, cos phieBlue illuminated display     One additional resettable counter Display for activ and reachtive power consumption intwo energy flow directions Display: I, U, P, S, F, cos phieBlue illuminated display, one
additional resettable counter,
display for active and
reactive power in two
energy flow directions,
Display: I, U, P, S, F, cos phi
2 counters:
1 x total, 1 x
resettable
CompatibilitySolar-Log 50, 300, 1200, 1900 and 2000Solar-Log 50,  300, 1200, 1900 and 2000
Warranty2 years2 years2 year1 year
Article number255913256059255914255346

Controlling Reactive Power & Recording Measurements

Utility Meter

The Solar-Log™ Utility Meter is a universal metering device. It can be integrated in both low- and medium-voltage networks (via a transformer) and is needed for various tasks. In addition to voltage-dependent reactive power control Q(U), it is also used for reactive power control at the feeding point and to record the data that is needed consumption meter for heavy loads.

Technical data
Voltage measurement17 V-520 V L-L, 4 inputs
Current measurementMax. 5A
InterfaceRS485
Rated operating voltage135-340 VDC voltage supply
MountingTop hat rails, 95-240 VAC /
135-340 VDC voltage supply
CompatibilitySolar-Log 300, 1200, 1900 and 2000
Warranty1 year